The new FLS M9.10 is a powerful monitor and transmitter designed to manage analog and frequency signals (or two analog signals) from every types of device which provide a 4-20mA or a frequency output. M9.10 is equipped with a wide full graphic display 4” which shows measured values clearly and a lot of other useful information. Moreover, due to a multicolor display plus a powerful backlight, measurement status can be determined easily from afar also. A tutorial software guarantees a mistake-proof and fast set up of every parameters. Calibration of 4-20mA input can be performed just fixing 2 points as well as 1 point or using a reference value through a new “in-line calibration”. Calibration of frequency input can be performed just fixing installation features or using a reference value through a new “in-line calibration”. Two independent 4-20mA outputs are available to remote measures to external devices. A proper combination of digital outputs (2 x SSR and 2 x relays) allows customized setups for any process to be controlled.
MAIN FEATURES
- Industrial waste water treatment
- Civil waste water treatment
- Water treatment processes
- Processing and Manufacturing industry
- Chemical processing
- Industrial environment with electromagnetic interferences
APPLICATIONS
- Wide graphic display
- Multicolor backlight
- Help on board
- Simultaneous visualization of two parameters
- Free setting of engineering unit
- Intuitive calibration procedure
- In line adjustment
- Able to handle active and passive analog signal
TECHNICAL DATA
General
- Associated sensors: FLS hall effect flow sensors with frequency output, FLS F6.60 Flow sensor magmeters and every devices which generate a passive or active 4-20mA signal.
- Materials:
- case: ABS
- display window: PC
- panel & wall gasket: silicone rubber
- keypad: 5-button silicone rubber
- Display:
- LC full graphic display
- backlight version: 3-colours
- backlight activation: User adjustable with 5 levels of timing
- update rate: 1 second
- enclosure: IP65 front
- Frequency input range (frequency): 0÷1000Hz
- Frequency accuracy (frequency): 0,5%
- Analog input range (frequency): 3,8÷21,0mA
- Analog input accuracy (frequency): 0,01mA
Electrical
- Supply Voltage: 12 to 24 VDC ± 10% regulated
- FLS hall effect flow Sensor power:
- 5 VDC @< 20 mA
- Optically isolated from current loop
- Short circuit protected
- 2 x Current input power:
- 18VDC @ ≤ 20mA
- 2 x Current output:
- 4-20 mA, isolated, fully adjustable and reversible
- Max loop impedance: 800 Ω @ 24 VDC - 250 Ω @ 12 VDC
- 2 x Solid State Relay output:
- User selectable as MIN alarm, MAX alarm, Pulse Out (only for frequency input), Window alarm, Off
- Optically isolated, 50 mA MAX sink, 24 VDC MAX pull-up voltage
- Max pulse/min: 300
- Hysteresis: User selectable
- 2 x Relay output:
- User selectable as MIN alarm, MAX alarm, Pulse Out (only for frequency input), Window alarm, Off
- Mechanical SPDT contact
- Expected mechanical life (min. operations): 107
- Expected electrical life (min. operations): 105 N.O./N.C. switching capacity 5A/240VAC
- Max pulse/min: 60
- Hysteresis: User selectable
Environmental
- Operating temperature: -20 to +70°C (-4 to 158°F)
- Storage temperature: -30 to +80°C (-22 to 176°F)
- Relative humidity: 0 to 95% not condensing 2 x Current output
Standards & Approvals
- Manufactured under ISO 9001
- Manufactured under ISO 14001
- CE
- RoHS Compliant
- GOST R